The Modbus plugin collects Discrete Inputs, Coils, Input Registers and Holding Registers via Modbus TCP or Modbus RTU/ASCII.
[[inputs.modbus]]
## Connection Configuration
##
## The plugin supports connections to PLCs via MODBUS/TCP or
## via serial line communication in binary (RTU) or readable (ASCII) encoding
##
## Device name
name = "Device"
## Slave ID - addresses a MODBUS device on the bus
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
slave_id = 1
## Timeout for each request
timeout = "1s"
## Maximum number of retries and the time to wait between retries
## when a slave-device is busy.
# busy_retries = 0
# busy_retries_wait = "100ms"
# TCP - connect via Modbus/TCP
controller = "tcp://localhost:502"
## Serial (RS485; RS232)
# controller = "file:///dev/ttyUSB0"
# baud_rate = 9600
# data_bits = 8
# parity = "N"
# stop_bits = 1
# transmission_mode = "RTU"
## Measurements
##
## Digital Variables, Discrete Inputs and Coils
## measurement - the (optional) measurement name, defaults to "modbus"
## name - the variable name
## address - variable address
discrete_inputs = [
{ name = "start", address = [0]},
{ name = "stop", address = [1]},
{ name = "reset", address = [2]},
{ name = "emergency_stop", address = [3]},
]
coils = [
{ name = "motor1_run", address = [0]},
{ name = "motor1_jog", address = [1]},
{ name = "motor1_stop", address = [2]},
]
## Analog Variables, Input Registers and Holding Registers
## measurement - the (optional) measurement name, defaults to "modbus"
## name - the variable name
## byte_order - the ordering of bytes
## |---AB, ABCD - Big Endian
## |---BA, DCBA - Little Endian
## |---BADC - Mid-Big Endian
## |---CDAB - Mid-Little Endian
## data_type - INT16, UINT16, INT32, UINT32, INT64, UINT64, FLOAT32-IEEE, FLOAT64-IEEE (the IEEE 754 binary representation)
## FLOAT32 (deprecated), FIXED, UFIXED (fixed-point representation on input)
## scale - the final numeric variable representation
## address - variable address
holding_registers = [
{ name = "power_factor", byte_order = "AB", data_type = "FIXED", scale=0.01, address = [8]},
{ name = "voltage", byte_order = "AB", data_type = "FIXED", scale=0.1, address = [0]},
{ name = "energy", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [5,6]},
{ name = "current", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [1,2]},
{ name = "frequency", byte_order = "AB", data_type = "UFIXED", scale=0.1, address = [7]},
{ name = "power", byte_order = "ABCD", data_type = "UFIXED", scale=0.1, address = [3,4]},
]
input_registers = [
{ name = "tank_level", byte_order = "AB", data_type = "INT16", scale=1.0, address = [0]},
{ name = "tank_ph", byte_order = "AB", data_type = "INT16", scale=1.0, address = [1]},
{ name = "pump1_speed", byte_order = "ABCD", data_type = "INT32", scale=1.0, address = [3,4]},
]
Metric are custom and configured using the discrete_inputs
, coils
,
holding_register
and input_registers
options.
The field data_type
defines the representation of the data value on input from the modbus registers.
The input values are then converted from the given data_type
to a type that is apropriate when
sending the value to the output plugin. These output types are usually one of string,
integer or floating-point-number. The size of the output type is assumed to be large enough
for all supported input types. The mapping from the input type to the output type is fixed
and cannot be configured.
These types are used for integer input values. Select the one that matches your modbus data source.
Use these types if your modbus registers contain a value that is encoded in this format. These types always include the sign and therefore there exists no variant.
These types are handled as an integer type on input, but are converted to floating point representation for further processing (e.g. scaling). Use one of these types when the input value is a decimal fixed point representation of a non-integer value.
Select the type UFIXED
when the input type is declared to hold unsigned integer values, which cannot
be negative. The documentation of your modbus device should indicate this by a term like
'uint16 containing fixed-point representation with N decimal places'.
Select the type FIXED
when the input type is declared to hold signed integer values. Your documentation
of the modbus device should indicate this with a term like 'int32 containing fixed-point representation
with N decimal places'.
(FLOAT32 is deprecated and should not be used any more. UFIXED provides the same conversion from unsigned values).
Modbus documentations are often a mess. People confuse memory-address (starts at one) and register address (starts at zero) or stay unclear about the used word-order. Furthermore, there are some non-standard implementations that also swap the bytes within the register word (16-bit).
If you get an error or don't get the expected values from your device, you can try the following steps (assuming a 32-bit value).
In case are using a serial device and get an permission denied
error, please check the permissions of your serial device and change accordingly.
In case you get an exception '2' (illegal data address)
error you might try to offset your address
entries by minus one as it is very likely that there is a confusion between memory and register addresses.
In case you see strange values, the byte_order
might be off. You can either probe all combinations (ABCD
, CDBA
, BADC
or DCBA
) or you set byte_order="ABCD" data_type="UINT32"
and use the resulting value(s) in an online converter like this. This makes especially sense if you don't want to mess with the device, deal with 64-bit values and/or don't know the data_type
of your register (e.g. fix-point floating values vs. IEEE floating point).
If nothing helps, please post your configuration, error message and/or the output of byte_order="ABCD" data_type="UINT32"
to one of the telegraf support channels (forum, slack or as issue).
$ ./telegraf -config telegraf.conf -input-filter modbus -test
modbus.InputRegisters,host=orangepizero Current=0,Energy=0,Frecuency=60,Power=0,PowerFactor=0,Voltage=123.9000015258789 1554079521000000000